Reflect-O-Ray® EDS Systems

Engineered Designed Systems
Vacuum Vented Radiant Heating Systems

Infra Spec® Home Page | Load Analysis | Industry Pricing | HELP

Please choose the system that best meets your needs:

** See diagram at bottom of page for tube length explanation **


3.5 Inch Relect-O-Ray®


 

BTU Capacity

Fan Motor

Number of Burners

Miscellaneous

75,000

1/6 H.P.

1

** See information below

75,000

1/4 H.P.

2

** See information below

75,000

1/2 H.P.

3

** See information below

75,000

1/2 H.P.

4

** See information below

105,000

1/6 H.P.

1

** See information below

105,000

1/4 H.P.

2

** See information below

105,000

1/2 H.P.

3

** See information below

105,000

1/2 H.P.

4

** See information below

130,000

1/6 H.P.

1

** See information below

130,000

1/4 H.P.

2

** See information below

130,000

1/2 H.P.

3

** See information below

130,000

1/2 H.P.

4

** See information below


6 Inch Relect-O-Ray®


 

BTU Capacity

Fan Motor

Number of Burners

Miscellaneous

240,000

1/2 H.P.

1

** See information below

240,000

1 H.P.

2

** See information below

360,000

1/2 H.P.

1

** See information below

360,000

1 H.P.

2

** See information below


Reflect-O-Ray® EDS 3.5®
General System Information

BURNER INPUT  130K/120K BTU/Hr 105,000 BTU/Hr 75,000
BTU/Hr
  Max. Min. Max. Min. Max. Min.
Standard Output System Radiant Pipe Between Any Burner & Vacuum Exhauster 90' 70' 80' 60' 70' 50'
High Output (Reduced Tube Length) Systems 80' 60' 70' 40' 60' 40'
Maximum Flows Through One Radiant Tube 2 3 4
Minimum Distance Before Elbow 35' 30' 25'
Minimum Distance Before Tee 40' 40' 40'
Minimum Distance Before Damper 30' 30' 30'

NOTE: Please contact factory for verification of any variations which may be needed.

Typical Two Burner System

 

Typical Four Burner System

Note: The total length of emitter tubing, which corresponds to a heater within a multiple-burner system, is the total distance between any Burner and the flue-venting exhaust fan (and subject to the Minimum & Maximum length parameters for a single heater in the "General System Information" chart, above). However, the Total Length of Emitter Tubing for the multiple-burner system is the sum of the actual emitter tubing per a specifier's system layout. Enter only the total actual number of feet of emitter tubing for Equipment Selection.


Reflect-O-Ray® EDS 6®
General System Information

BURNER INPUT  360,000
BTU/Hr
240,000
BTU/Hr
  Max. Min. Max. Min.
Standard Output System Radiant Pipe Between Any Burner & Vacuum Exhauster 230' 180' 200' 150'
High Output (Reduced Tube Length) Systems 190' 150' 160' 130'
Maximum Flows Through One Radiant Tube 2 2
Minimum Distance Before Elbow 30' 30'
Minimum Distance Before Tee 40' 40'
Minimum Distance Before Damper 30' 30'

NOTE: Please contact factory for verification of any variations which may be needed.

Typical Two Burner System

ror6fig.gif (3330 bytes)

Note: The total length of emitter tubing, which corresponds to a heater within a multiple-burner system, is the total distance between any Burner and the flue-venting exhaust fan (and subject to the Minimum & Maximum length parameters for a single heater in the "General System Information" chart, above). However, the Total Length of Emitter Tubing for the multiple-burner system is the sum of the actual emitter tubing per a specifier's system layout. Enter only the total actual number of feet of emitter tubing for Equipment Selection.